The effect of shared condensate lines on steam trap behavior

Have more questions? Submit a request
 
Some steam traps drain their condensate to shared lines, meaning the behavior of one trap can affect others.
 
Consider the following example:
 
Slide1.PNG
When the system is functioning properly, we see condensate traveling through the blue paths to the receiver tank.
 
When a trap fails, we'll see elevated temperatures near the outlet of the trap.  Like this diagram:
 
Slide2.PNG
 
In some cases, depending on the plumbing, pressures, and design of the steam system, one trap may be close enough to bias another, that would look like this:
 
Slide3.PNG
In some cases, this bias only affects the measurement at the sensor, and can be ignored.  In other cases, if the trap is designed to work at a specific pressure, such as a Thermostatic, Thermodynamic, Balanced Pressure, or Orifice trap, the change in pressure in the system could be causing an otherwise good trap to fail.
 
The best strategy to prevent this behavior is to install a check valve downstream from the steam trap.
 
Shared_Condensate_Lines.png
 
 
 

Articles in this section

Was this article helpful?
1 out of 1 found this helpful
Share

Comments

0 comments

Please sign in to leave a comment.